The Mitsubishi Electric PUMY-SP112VKMD-AR1 is a powerful 12.5 kW multi head outdoor unit designed for maximum efficiency and performance. This single fan heat pump VRF outdoor unit is compact, allowing for installation in confined spaces with a 27% reduction in height and 25% reduction in weight compared to dual fan models. It supports connections from any of four directions, enhancing flexibility in design. With super quiet mode, noise levels can be reduced by up to 10dB(A), making it suitable for residential zones. This unit offers excellent energy efficiency, connectivity with various indoor units, and a robust build for reliable year-round performance.
Model: PUMY-SP112VKMD
| MODEL | PUMY-SP112VKMD | |||
| Power Source | 1-phase 220-230-240 V, 50 Hz; 1-phase 220 V, 60 Hz | |||
| Cooling Capacity (Nominal) | ||||
| *1 | kW | 12.5 | ||
| *1 | BTU/h | 42650 | ||
| Power Input | kW | 3.10 | ||
| Current Input | A | 14.38-13.75-13.18, 14.38 | ||
| AEER/EER | kW/kW | 3.31 / 4.03 | ||
| Temp Range cooling | ||||
| Indoor Temp. | WB | 15 to 24C | ||
| Outdoor Temp. | D.W | -5 to 52C *4,*5 | ||
| Heating Capacity (Nominal) | ||||
| *2 | kW | 14.0 | ||
| *2 | BTU/h | 47,768 | ||
| Power Input | kW | 3.17 | ||
| Current Input | A | 14.70-14.06-13.48, 14.70 | ||
| ACOP/COP | kW/kW | 3.72 / 4.42 | ||
| Temp Range of Heating | ||||
| Indoor Temp | W.B | 15 to 27C | ||
| Outdoor Temp | W.B | -20 to 15C | ||
| Indoor Unit Connectable | ||||
| Total capacity | 50 to 130% of outdoor unit capacity | |||
| Model/ Quantity | ||||
| City Multi | P15-P140/9 | |||
| Branch Box | P15-P100/8 | |||
| Mixed System | ||||
| Branch Box 1 unit | City Multi | P15-P140/5 | ||
| Branch Box | P15-P100/5 | |||
| Branch Box 2 Unit | City Multi | P15-P140/3 or 2 *8 | ||
| Branch Box | P15-P100/7 or 8 *8 | |||
| Sound Pressure Level (Cooling/Heating) db<A> | 52/54 | |||
| Sound Power Level (Cooling) db<A> | 72 | |||
| Refrigerant Piping Diameter | ||||
| Liquid Piping | Mm | 9.52 Flare | ||
| Gas piping | Mm | 15.88 Flare | ||
| FAN | ||||
| Type x quantity | Propeller Fan _ 1 | |||
| Air flow rate | ||||
| m_/min | 77 | |||
| L/s | 1283 | |||
| Cfm | 2719 | |||
| External Static Pres | 0Pa , 30Pa *9 | |||
| Compressor | Type x Quantity | Twin rotary hermetic compressor _ 1 | ||
| Starting method | Inverter | |||
| Motor Output kW | 3.1 | |||
| External Finish | Galvanized Steel Sheet Munsell No. 3Y 7.8/1.1 | |||
| External Dimensions H x W x D | Mm | 981 _ 1,050 _ 330 (+25) | ||
| Protection Devices | ||||
| High Pressure Protection | High pressure Switch | |||
| Inverter circuit (COP/FAN) | Overcurrent detection, Overheat detection (Heat sink thermistor) | |||
| Compressor | Compressor thermistor, Over current detection | |||
| Fan motor | Overheating. Voltage protection | |||
| Refrigerant | ||||
| Type | R410A | |||
| Pre-Charged Quantity (kg) | 3.5 kg | |||
| Net weight(kg) | 93 | |||
| Heat Exchanger | Cross Fin and Copper tube | |||
| Defrosting Method | Reversed refrigerant circuit | |||
| Optional Parts | Joint: CMY-Y62-G-E Header: CMY-Y64/68-G-E | |||