The Daikin FHA85C-VC2V 8.5kW SkyAir ceiling suspended air conditioner is designed for seamless integration in commercial and residential spaces. This energy-efficient system offers both cooling and heating capabilities, ensuring optimal comfort year-round. Equipped with a backlit controller, it provides intuitive and convenient operation. With robust construction and advanced features, the Daikin FHA85C-VC2V is a reliable solution for maintaining an ideal indoor climate.
Indoor Unit: FHA85CVMA
Outdoor Unit: RZAV85C2V1
| Model Name | Indoor unit | FHA85CVMA |
| Outdoor unit | RZAV85C2V1 | |
| Power supply | 1 Phase, 220-240V, 50Hz | |
| Cooling capacity1,3 Rated (Min. – Max.) | kW | 8.5 (4.0-10.0) |
| Heating capacity2,3 Rated (Min. – Max.) | kW | 10.0 (4.1-11.2) |
| Power consumption | Cooling 1 – KW | 2.51 |
| Heating 2 – KW | 2.75 | |
| EER | Cooling – kW/kW | 3.39 |
| COP | Heatin – kW/kW | 3.64 |
| AEER | Cooling | 3.32 |
| ACOP | Heating | 3.57 |
| TCSPF (Cooling) Commercial / Residential | Hot | 5.22 / 4.79 |
| Average | 5.27 / 4.25 | |
| Cold | 5.63 / 4.37 | |
| HSPF (Heating) Commercial / Residential | Hot | 4.59 / 4.58 |
| Average | 4.31 / 4.12 | |
| Cold | 3.95 / 3.71 | |
| Indoor unit | Colour – Unit | White |
| Airflow rate (H / HM / M / ML / L) l/s | 467 / 433 / 400 / 367 / 333 | |
| Airflow rate (H / HM / M / ML / L) m3/min | 28.0 / 26.0 / 24.0 / 22.0 / 20.0 | |
| Sound pressure level4 (H / HM / M / ML / L) dB(A) | 0 42.0 / 40.0 / 38.0 / 36.0 / 34.0 4 | |
| Dimensions (HXWXD) Unit mm | 235X1,590X690 | |
| Machine weight Unit Kg | 38 | |
| Certified operation range Cooling CWB | 14 to 25 | |
| Certified operation range Heating CDB | 15 to 27 | |
| Outdoor unit | Colour | Ivory White |
| Compressor – Type | Hermetically sealed swing type | |
| Compressor – Motor output kW | 3.3 | |
| Refrigerant charge (R-32) kg | 2.90 (Charged for 30 m) |
|
| Sound pressure level 4 – Cooling / Heating – dB(A) | 52 / 53 | |
| Sound pressure level 4 – Night quiet mode – dB(A) | 48 | |
| Sound power level dB(A) | 71 | |
| Dimensions (HXWXD) MM | 990X940X320 | |
| Machine weight Kg | 78 | |
| Certified operation range Coolig CDB | -5 to 50 | |
| Certified operation range Heating CWB | -15 to 15.5 | |
| Piping connections | Liquid (Flare) mm | o/ 9.5 |
| Gas (Flare) | o/ 15.9 | |
| Drain Indoor Unit – mm | VP20 (I.D.o/ 20XO.D.o/ 26) | |
| Drain Outdoor Unit – mm | Connectable hose I.D. o/ 25 | |
| Max. interunit piping length | m | 75 (Equivalent length 90) |
| Max. installation height difference | m | 30 |
| Heat insulation | Both liquid and gas piping | |