The Fujitsu SET-AUTH45KRTA 12.5kW inverter cassette split system air conditioner is designed for powerful performance and efficiency. With a robust 3-phase power supply, it delivers 12.5kW of cooling and 14kW of heating, ensuring optimal comfort in both residential and commercial settings. The system features reverse cycle operation, advanced moisture removal and quiet indoor operation, making it a reliable choice for Australian climates. Equipped with R32 refrigerant and a high-performance grille, it provides precision climate control with minimal environmental impact.
Indoor Unit: AUTH45KRTA
Outdoor Unit: AOTH45KRTA
Grille: UTG-UKTB-W
Wired Controller: UTY-LBTYC
Indoor unit |
AUTH45KRTA |
| Outdoor unit | AOTH45KRTA |
| Operation Type | Reverse Cycle |
| Power Source V/Ph/Hz | 400 / 3 / 50 |
| Cooling Capacity kW (Rated (Min – Max)) | 12.50 (4 – 14) |
| Heating Capacity kW (Rated (Min – Max)) | 14.00 (4.2 – 16.5) |
| Input Power Cooling kW (Rated (Min – Max)) | 3.89 (4.9) |
| Input Power Heating kW (Rated (Min – Max)) | 3.89 (4.9) |
| EER Cooling kW/kW | 3.21 |
| COP Heating kW/kW | 4.07 |
| Star Rating Cooling (0-10) (Hot / Average / Cold) | 3 / 3 / 3 |
| Star Rating Heating (0-10) (Hot / Average / Cold) | 3.5 / 2.5 / 2 |
| Total Cooling Seasonal Performance Factor Residential kW (Hot / Average / Cold) | 4.764 / 4.548 / 4.842 |
| Heating Seasonal Performance Factor Residential kW (Hot / Average / Cold) | 5.119 / 5.331 / 5.773 |
| Total Cooling Seasonal Performance Factor Commercial kW (Hot / Average / Cold) | 5.119 / 5.331 / 5.773 |
| Heating Seasonal Performance Factor Commercial kW (Hot / Average / Cold) | 5.139 / 4.658 / 4.043 |
| Running Current amps (Cooling / Heating) | 6.4 / 5.5 |
| Moisture Removal l/hr | 4.8 |
| Indoor Sound Pressure Cooling dBA (High / Quiet) | 46 / 36 |
| Indoor Sound Pressure Heating dBA (High / Quiet) | 46 / 36 |
| Outdoor Sound Pressure dBA (Cooling / Heating) | 55 / 57 |
| Outdoor Sound Power dBA | 71 |
| Air Circulation (Indoor – High Fan) Cooling l/sec | 542 |
| Air Circulation (Indoor – High Fan) Heating l/sec | 542 |
| Indoor Unit Dimensions mm (Height x Width x Depth) | 288 x 840 x 840 |
| Indoor Unit Weight kg | 29 |
| Outdoor Unit Dimensions mm (Height x Width x Depth) | 998 x 940 x 320 |
| Outdoor Unit Weight kg | 67 |
| Grill Weight | 6 |
| Piping Connects mm Ø (Liquid / Gas) | 9.52 / 15.88 |
| Pipe Length m (Max (Precharged)) | 50 (30) |
| Max Height Difference m | 30 |
| Operation Range Cooling °CDB (Min to Max) | -10 to 50 |
| Operation Range Heating °CDB (Min to Max) | -15 to 24 |
| Refrigerant Type | R32 |
| Refrigerant Amount g | 2,180 |